Pull Test Information
Cable on Cable vs. Cable in Fabric Innerduct
Test Conditions & Method
Cable Spec
13 mm OD PE Fiber Optic cable
Outer Duct Spec
50 mm ID PE Pipe
MaxCell
®
Spec
52mm 2-Cell
Cable Pulling Tension
140 kg
Cable Pulling Speed
25 meters / min
Cable Pulling Duration
10 minutes (equivalent of 250 meter pull)
20 minutes (equivalent of 500 meter pull)
30 minutes (equivalent of 750 meter pull)
Test Method
Fix cable within the PE subduct
Rotate another 13mm cable over the fixed cable at a fixed speed and tension. Verify the cables cross each other at some point. Check sheath damage; (250m, 500m, 750m)
Fix the cable within fabric innerduct. Rotate another 13mm cable through the second cell at fixed parameters
Test Results
Cable on Cable 250m
Pass
Cable on Cable 500m
Fail
Cable on Cable 750m
Fail
Cable in Fabric Innerduct 750m
Pass
Pass Fail Criteria : Having no significant external damage on the cable sheath
Cable on Cable
Minor abrasion at 250m but significant sheath damage at 500m and 750m
Large amounts of PE flaking observed over longer distances
Higher pulling tensions and longer pulls may lead to possible signal failure
Cable in Fabric Innerduct
Very minor abrasion observed on the sheath
Fabric Innerduct showed a small 75mm tear right where the cables crossed but the tear did not expose the cable to any significant damage Note: The cable was in a 10m continuous loop. Because of this loop the MaxCell saw the head of the cable pass over a minimum of 75 times during the experiment
Higher pulling tensions and longer pulls possible without damage to the cable
Control: Cable Observation Before Test
Cable Observation After Test